![Toshiba MMY-MAP0724HT6UL Скачать руководство пользователя страница 169](http://html.mh-extra.com/html/toshiba/mmy-map0724ht6ul/mmy-map0724ht6ul_service-manual_1134809169.webp)
168
(5)Display of Indoor Unit Information (Displayed on Header Unit Only)
Note:
Indoor address No. is selected by setting SW02 and SW03 and displayed on 7-segment display, section A.
* Although 64 indoor unit addresses (Nos. 01-64) are theoretically available, the number of indoor units that can
be connected to the same refrigerant piping system is limited to 48.
(6)Display of Outdoor EEPROM Writing Error Code (Displayed on Header Unit Only)
* The latest error code written in the EEPROM of each outdoor unit is displayed.
(This function is used to check the error code after the resetting of the power supply.)
To display the error code, press SW04 and hold for at least 5 seconds after setting SW01 to 03 as shown in the
table below.
• 7-Segment Display
Set SW01/SW02/SW03 to [1/1/16] and press SW04 and hold for at least 5 seconds. The latest error code of the
header unit (U1) will be displayed.
If the setting of SW02 is changed, the latest error code of a follow unit (U2-U4) will be displayed.
SW01 SW02 SW03
Display detail
4
1~16
1~3
Indoor BUS communication signal
receiving status
B Upon receiving signal: [… … 1], Other times: [… … …]
5
Indoor check code
B No check code: [– – –]
6
Indoor capacity
B
0.6 to 4.5
7
Indoor request command
(S code, operation mode)
B [ #. …
∗
]
# represents mode:
COOL: [C. …
∗
], HEAT: [H. …
∗
]
FAN: [F. …
∗
], OFF: [S. …
∗
]
∗
represents S code: [#. … 0] to [#. … F]
8
Indoor PMV opening data
B Displayed in decimal format
9
Indoor TA sensor data
B Displayed in decimal format
11
Indoor TCJ sensor data
B Displayed in decimal format
12
Indoor TC1 sensor data
B Displayed in decimal format
13
Indoor TC2 sensor data
B Displayed in decimal format
SW03
SW02
Indoor address
7-segment display section A
1
1~16
SW02 setting number
[01]~[16]
2
1~16
SW02 setting 16
[17]~[32]
3
1~16
SW02 setting 32
[33]~[48]
SW01
SW02
SW03
Indoor address
7-segment display section A
1
1
16
Latest error code of header unit (U1)
E. 1.
∗∗∗
2
Latest error code of follower unit No. 1 (U2)
E. 2.
∗∗∗
3
Latest error code of follower unit No. 2 (U3)
E. 3.
∗∗∗
4
Latest error code of follower unit No. 3 (U4)
E. 4.
∗∗∗
Section A
Section B
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...