113
Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration
(e.g. a Super heat recovery multi system). For details, see the service manual for the outdoor unit.
Check code
Display of receiving unit
Typical fault site
Description of error
Outdoor 7-segment display
TCC-LINK
central control
or wired
remote control
display
Indicator light block
Sub-code
Flash
F13
01: Compressor 1
02: Compressor 2
03: Compressor 3
F13
ALT
Error in temperature
sensor built into indoor
IGBT (TH)
Temperature sensor built into indoor IGBT (TH)
has been open/short-circuited.
H01
01: Compressor 1
02: Compressor 2
03: Compressor 3
H01
Compressor breakdown
Inverter current (Idc) detection circuit detects
overcurrent.
H02
01: Compressor 1
02: Compressor 2
03: Compressor 3
H02
Compressor error (lockup)
Compressor lockup is detected
A3-IPDU related errors
H03
01: Compressor 1
02: Compressor 2
03: Compressor 3
H03
Current detection circuit
error
Abnormal current is detected while inverter
compressor is turned off.
P04
01: Compressor 1
02: Compressor 2
03: Compressor 3
P04
ALT
Activation of high-pressure
SW
High-pressure SW is activated.
P07
01: Compressor 1
02: Compressor 2
03: Compressor 3
P07
ALT
Heat sink overheating
error
Temperature sensor built into IGBT (TH) detects
overheating.
P22
0
∗
: IGBT circuit
1
∗
: Position detection circuit error
3
∗
: Motor lockup error
4
∗
: Motor current detection
C
∗
: TH sensor error
D
∗
: TH sensor error
E
∗
: Inverter DC voltage error
(outdoor fan)
Note: Although letters 0 to F appear
at locations indicated by “
∗
”,
please ignore them.
P22
ALT Outdoor fan IPDU error
Outdoor fan IPDU detects error.
P26
01: Compressor 1
02: Compressor 2
03: Compressor 3
P26
ALT
Activation of G-Tr (IGBT)
short-circuit protection
Short-circuit protection for compressor motor
driver circuit components is activated (momentary
overcurrent).
P29
01: Compressor 1
02: Compressor 2
03: Compressor 3
P29
ALT
Compressor position
detection circuit error
Compressor motor position detection error is
detected.
Operation Timer
Ready
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...