204
2
Propeller fan
Fan motor
(continued)
10)Disconnect the faston connectors for the
fan motor leads (3 pieces) from the Fan
IPDU, and pull the leads up and out.
11)Remove the fan motor.
(M6 × 0.8’ (20 mm), 4 pcs.)
2. CAUTION for replacement or
attachment
1) Insert the propeller fan while aligning the D-
cut surface of the fan motor shaft with the
arrow mark (
) on the fan.
(If the propeller fan is tightly mounted on the
shaft without securing alignment between
the D-cut surface and the arrow mark (
),
it may cause the fan to melt and fall off due
to friction heat.)
2) Be sure to put the square washer in place.
(Otherwise, unusual noises and vibrations
may result.)
3) Tighten the flange nut at a torque of 11.1
ft•lbs (15 N•m).
(To tighten the flange nut, turn it
counterclockwise.)
No. Part to be replaced
Work procedure
Remarks
Disconnect faston
connectors and pull fan
motor leads up and out.
11) Screw (4 locations)
Fan motor lead
travel route
Fan IPDU
Close-up view of faston
connectors
D-cut surface of fan
motor shaft
Arrow mark (
) of fan
To be aligned with D-cut surface
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...