129
Check code
Location
of
detection
Description
System status
Error detection condition(s)
Check items (locations)
Wired
remote
control
Outdoor 7-segment display
Check
code
Sub-code
P22
P22
0
∗
: IGBT circuit
1
∗
: Position
detection circuit
error
3
∗
: Motor lockup
error
4
∗
: Motor
current
detection
C
∗
: TH sensor
temperature
error
D
∗
: TH sensor
error
E
∗
: Inverter DC
voltage error
(outdoor fan)
Note:
Although
letters 0 to F
appear at
locations
indicated by
“
∗
”, please
ignore them.
IPDU
Outdoor fan
IPDU error
All stop
(Sub code: 0
∗
)
Fan IPDU over current protection
circuit
Flow of current equal to or greater
than the specified value is detected
during startup of the fan.
• Check fan motor.
• Check for defect in fan IPDU P.C.
board.
All stop
(Sub code: 1
∗
)
Fan IPDU position detection circuit
Position detection is not going on
normally.
• Check fan motor.
• Check connection of fan motor
connector.
• Check for defect in fan IPDU P.C.
board.
All stop
(Sub code: 3
∗
)
Gusty wind, an obstruction, or
another external factor
Speed estimation is not going on
normally.
• Check fan motor.
• Check for defect in fan IPDU P.C.
board.
All stop
(Sub code: 4
∗
)
Fan IPDU over current protection
circuit
Flow of current equal to or greater
than the specified value is detected
during operation of the fan.
• Check fan motor.
• Check connection of fan motor
connector.
• Check for defect in fan IPDU P.C.
board.
All stop
(Sub code: C
∗
)
Higher temperature than the
specified value is detected during
operation of the fan.
• Check fan motor.
• Check for defect in fan IPDU P.C.
board.
All stop
(Sub code: D
∗
)
The resistance value of the sensor
is infinite or zero (open or short
circuit).
• Check for defect in fan IPDU P.C.
board.
All stop
(Sub code: E
∗
)
Fan IPDU DC voltage protection
circuit
The DC voltage higher or lower than
the specified value is detected.
• Check power voltage of the main
power supply.
• Check for defect in fan IPDU P.C.
board.
• Check connection of fan IPDU
P.C. board.
P26
P26
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
IPDU
G-TR short-
circuit
protection error
All stop
Overcurrent is momentarily
detected during startup of
compressor.
• Check connector connection and
wiring on A3-IPDU P.C. board.
• Check for defect in compressor
(layer short-circuit).
• Check for defect in outdoor P.C.
board (A3-IPDU).
P29
P29
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
IPDU
Compressor
position
detection circuit
error
All stop
Position detection is not going on
normally.
• Check wiring and connector
connection.
• Check for compressor layer
short-circuit.
• Check for defect in A3-IPDU P.C.
board.
P31
–
–
Indoor
unit
Other indoor
error
(group follower
unit error)
Stop of
corresponding
unit
There is error in other indoor unit in
group, resulting in detection of E07/
L07/L03/L08.
• Check indoor P.C. board.
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...