13
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of
refrigerant.
Calculation of additional refrigerant charge amount
Table 3
Table 4
Example:
(114 type)
Additional refrigerant charge
amount
(lb)
=
Actual length of liquid
pipe
×
Additional refrigerant charge
amount per liquid pipe 1ft
[Table 3]
+
Adjustment amount of
refrigerant
[Table 4]
Liquid pipe outer dia.
Ø1/4
Ø3/8
Ø1/2
Ø5/8
Ø3/4
Additional refrigerant amount / 1 ft (lb)
0.017
0.037
0.071
0.108
0.168
Outdoor unit capacity type
Adjustment amount of refrigerant
(lb)
Combined outdoor units
072 type
3.31
072 type
–
096 type
13.23
096 type
–
114 type
15.43
114 type
–
144 type
0.00
072 type
072 type
168 type
16.53
096 type
072 type
192 type
27.56
096 type
096 type
228 type
27.56
114 type
114 type
L1
Ø1/2: 30 ft
L2
Ø1/2: 15 ft
L3
Ø3/8: 10 ft
a
Ø1/4: 10 ft
b
Ø3/8: 15 ft
c
Ø1/4: 10 ft
d
Ø1/4: 10 ft
Additional charge amount (lb)
=
(Lx
×
0.017 lb/ft) + (Ly
×
0.037 lb/ft) + (Lz X 0.071 lb/ft) + (15.43 lb)
=
((a+c+d)
×
0.017 lb)+((L3+b)
×
0.037 lb)+((L1+L2)
×
0.017 lb+(15.43 lb)
=
(30
×
0.017 lb) + (25
×
0.037 lb) + (45
×
0.071 lb) + (15.43 lb)
=
20.06 lb
Lx : Actual total length of liquid pipe Ø1/4 (ft)
Ly : Actual total length of liquid pipe Ø3/8 (ft)
Lz : Actual total length of liquid pipe Ø1/2 (ft)
L2
L3
a
b
c
d
L1
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...