125
Check code
Location
of
detection
Description
System status
Error detection condition(s)
Check items (locations)
Wired
remote
control
Outdoor 7-segment display
Check
code
Sub-code
L03
–
–
Indoor
unit
Duplicated
indoor header
unit
Stop of
corresponding
unit
There is more than one header unit
in group.
• Check indoor addresses.
• Check for any change made to
remote control connection
(group/individual) since indoor
address setting.
L04
L04
–
I/F
Duplicated
outdoor line
address
All stop
There is duplication in line address
setting for outdoor units belonging
to different refrigerant piping
systems.
• Check line addresses.
L05
–
–
I/F
Duplicated
priority indoor
unit (as
displayed on
priority indoor
unit)
All stop
More than one indoor unit has been
set up as priority indoor unit.
• Check display on priority indoor
unit.
L06
L06
No. of priority
indoor units
I/F
Duplicated
priority indoor
unit (as
displayed on
indoor unit
other than
priority indoor
unit)
All stop
More than one indoor unit have
been set up as priority indoor unit.
• Check displays on priority indoor
unit and outdoor unit.
L07
–
–
Indoor
unit
Connection of
group control
cable to stand-
alone indoor
unit
Stop of
corresponding
unit
There is at least one stand-alone
indoor unit to which group control
cable is connected.
• Check indoor addresses.
L08
L08
–
Indoor
unit
Indoor group /
addresses not
set
Stop of
corresponding
unit
Address setting has not been
performed for indoor units.
• Check indoor addresses.
• This code is displayed when
power is turned on for the first
time after installation.
L09
–
–
Indoor
unit
Indoor capacity
not set
Stop of
corresponding
unit
Capacity setting has not been
performed for indoor unit.
Set indoor capacity. (DN = 11)
L10
L10
–
I/F
Outdoor
capacity not set
All stop
Jumper wire provided on P.C. board
for servicing I/F P.C. board has not
been removed as required for given
model.
Check model setting of P.C. board
for servicing outdoor
I/F P.C. board.
L20
–
–
Indoor
unit
Duplicated
central control
address
All stop
There is duplication in central
control address setting.
• Check central control addresses.
L17
L17
–
I/F
Inconsistent
models of
outdoor units
1 and 2 series outdoor units have
been mixed.
• Check outdoor units.
L28
L28
–
I/F
Too many
outdoor units
connected
All stop
There are more than four outdoor
units.
• Check No. of outdoor units
connected (Only up to 4 units per
system allowed).
• Check communication lines
between outdoor units.
• Check for defect in outdoor P.C.
board (I/F).
L29
L29
Symbol O
signifies site of
IPDU error.
I/F
Error in No. of
IPDUs
All stop
Insufficient number of IPDUs are
detected when power is turned on.
• Check model setting of P.C.
board for servicing outdoor I/F
P.C. board.
• Check connection of UART
communication connector.
• Check A3-IPDU, fan IPDU, and I/
F P.C. board for defect.
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...