Table: Function selecting item numbers (DN)
(Items necessary to perform the applied control at the local site are described.)
DN
01
02
03
04
06
0d
0F
10
11
12
13
14
1E
28
2A
2E
31
32
33
Item
Filter display delay timer
Dirty state of filter
Central control address
Specific indoor unit
priority
Heating temp shift
Existence of [AUTO]
cool / heat mode
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Temp difference of [AUTO]
mode selection COOL
→
HEAT, HEAT
→
COOL
Automatic restart of
power failure
Selection of option/error
input (CN80)
HA terminal (CN61)
select
Ventilating fan control
TA sensor selection
Temperature unit select
Description
0000 : None
0001 : 150H
0002 : 2500H
0003 : 5000H
0004 : 10000H
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0001 : No.1 unit
to
0064 : No.64 unit
0099 : Unfixed
0000 : No priority
0001 : Priority
0000 : No shift 0001 : +1°C
0002 : +2°C
to
0003 : +3°C
0010 : +10°C
(Up to +6 recommended)
0000 : Provided
0001 : Not provided (Automatic selection from connected outdoor unit)
0000 : Heat pump
0001 : Cooling only (No display of [AUTO] [HEAT])
0018: Console
0000 : Unfixed
0001 to 0034
0001 : No.1 unit
to
0030 : No.30 unit
0001 : No.1 unit
to
0064 : No.64 unit
0000 : Individual
0001 : Header unit of group
0002 : Follower unit of group
0000 : 0 deg
to
0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None
0001 : Restart
0000 : Filter input
0001 : Alarm input (Air washer, etc.)
0002 : Outside error input
0000 : Usual
0001 : Leaving-ON prevention control
0002 : Fire alarm input
0000 : Unavailable
0001 : Available
0000 : Body TA sensor
0001 : Remote controller sensor
0000 : °C (at factory shipment)
0001 : °F
At shipment
0001 : 150H
0000 : Standard
0099 : Unfixed
0000 : No priority
0000 : No shift
0001 : Not provided
0000 : Heat pump
Depending on model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
0003 : 3 deg
(Ts±1.5)
0000 : None
0002 : Outside error input
(Interlock)
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Body TA sensor
0000 : °C
49
Содержание MML-AP0074NH-E
Страница 14: ...5 Hz Φ Φ Φ 2 SPECIFICATIONS 2 1 Indoor Unit 13 ...
Страница 15: ...6 Hz Φ Φ Φ 14 ...
Страница 132: ...TOSHIBA CARRIER THAILAND CO LTD ...