10-4. Check Code and Check Position Displayed on the Remote Controller and Outdoor Unit
(7-Segment Display of Interface)
<In case of SUPER MODULAR MULTI SYSTEM>
Check code
Wired
remote
controller
E01
E02
E03
E04
E06
—
E08
E09
E10
E12
Outdoor 7-segment display
Check code
Auxiliary code
—
—
—
—
—
—
—
—
E06
No. of indoor units
which received
signal normally
E07
—
E08
Duplicated indoor
addresses
—
—
—
—
E12
01: Indoor/outdoor
communication
02: Between outdoors
communication
Detected
position
Remote
controller
Remote
controller
Indoor
unit
Indoor
unit
I/F
I/F
Indoor
I/F
Remote
controller
Indoor
unit
I/F
Check code name
Communication error between
indoor and remote controller
(Detected at remote controller side)
Remote controller sending error
Communication error between
indoor and remote controller
(Detected at indoor side)
Indoor/outdoor communication
circuit error
(Detected at indoor side)
Decreased number of indoor units
Indoor/outdoor communication
circuit error
(Detected at outdoor side)
Duplicated indoor addresses
Duplicated master remote
controllers
Communication error between
indoor P.C. board assembly
Automatic address start error
Status
Corresponding
unit only stops.
Corresponding
unit only stops.
Corresponding
unit only stops.
Corresponding
unit only stops.
All stop
All stop
All stop
Corresponding
unit only stops.
Corresponding
unit only stops.
All stop
Error detection condition
Communication interrupted between
indoor P.C. board and remote controller.
Signal could not be sent from remote
controller to indoor unit.
No communication from remote
controller (including wireless) and
communication adapter.
Indoor unit does not receive
communication from outdoor unit.
When signal is not sent for a certain
period from the indoor unit which has
been used to send signals.
Transmission from outdoor to indoor
cannot continue for 30 seconds.
Multiple indoor unit address setup are
duplicated.
In 2-remote controller control (including
wireless), both are setup as master
(Header indoor unit stops and other
indoor unit is operating.)
Communication was not succeeded
after power was supplied or during
communication.
• When indoor automatic address
started, other refrigerant circuit system
was setting automatic address.
• When outdoor automatic address
started, indoor automatic address
was executed.
Check item (position)
• Check remote controller inter-unit cable (A/B).
• Check disconnection, connector contact error.
• Check indoor power supply.
• Check indoor P.C. board error.
• Check remote controller address setup.
(When two remote controllers operate)
• Check remote controller P.C. board.
• Check the communication wire of remote controller:
Exchange remote controller.
• Check remote controller and communication adapter wiring.
• Check power-ON order of indoor/outdoor.
• Check indoor address setup.
• Check inter-unit cabling between indoor and outdoor.
• Check outdoor end terminal resistance setup (SW30-2).
• Check the power supply of indoor unit. (Power-ON)
• Check connection of communication line between indoor and outdoor.
• Check connector connection for communication in indoor P.C. board.
• Check connector connection for communication in outdoor P.C. board.
• Check indoor P.C. board failure.
• Check outdoor P.C. board (I/F) failure.
• Check outdoor terminator resistor setup (SW30-2).
• Check the communication connection between indoor and outdoor.
• Check indoor address.
• Check the change of remote controller connection (Group / individual)
after setup of indoor address.
• Check remote controller setup.
• Check remote controller P.C. board.
• Indoor P.C. board failure
• Setup the address again after disconnecting communication
connection with other refrigerant circuit system.