6
2
[Remote controller detects error.]
(
∗
)
¡
: Goes on,
¥
: Flashes,
l
: Goes off
A (Alternate)
: Flashing condition is alternate when there are two flashing LED.
S (Simultaneously) : Two LED flash simultaneously when there are two flashing LED.
[Central controller detects error.]
Note)
The check code display may be different according to the detected device even same error contents such as communication error.
Check code display
Remote controller
E01
E02
E09
Outdoor 7-segment
Auxiliary code
—
—
—
—
—
—
Sensor lamp display
Block display (
∗
)
Operation Timer
Ready
Flash
¥
l
l
¥
l
l
¥
l
l
Main defective position
No remote controller header unit, remote controller
communication (receive) error
Remote controller communication (send) error
Duplicated remote controller header
Description
When signal cannot be received from indoor unit, when header of remote
controller was not set (including 2 remote controllers)
When signal cannot be sent to indoor unit
In 2-remote controller control, both remote controllers were set to header.
(Indoor header stops with alarm and follower unit continues operation.)
Check code display
TCC-LINK central
C05
C06
—
C12
P30
Outdoor 7-segment
Auxiliary code
—
—
—
—
—
—
—
—
—
—
Sensor lamp display
Block display (
∗
)
Operation Timer
Ready
Flash
Is not displayed
(In shared use
of remote controller)
—
According to unit with alarm
(Abovementioned)
Main defective position
Central control system communication (send) error
Central control system communication (receive) error
There are multiple network adapters.
Batched alarm of interface for general-purpose equipment control
Group follower unit error
Description
When signal of central control system cannot be sent, there are same multiple
central devices (AI-NET)
When signal of central control system cannot be received
There were multiple network adapters (AI-NET) on remote controller
communication line.
Error of equipment connected to control interface of the general-purpose unit
exclusive to TCC-LINK/AI-NET
Group follower unit error
(For remote controller, [
∗∗∗
] details is displayed together with unit No.)
Содержание MML-AP0074NH-E
Страница 14: ...5 Hz Φ Φ Φ 2 SPECIFICATIONS 2 1 Indoor Unit 13 ...
Страница 15: ...6 Hz Φ Φ Φ 14 ...
Страница 132: ...TOSHIBA CARRIER THAILAND CO LTD ...