No.
14
15
Item
Display of
[
OPERATION
READY]
[ PRE-HEAT]
Selection of
central control
mode
Outline of specifications
<OPERATION READY>
Displayed on the remote controller
1) When the following check codes are indicated
• Open phase of power supply wiring [P05] was detected.
• There is an indoor unit that detected the indoor
overflow [P10].
• There is an indoor unit that detected the interlock alarm
[L30].
2) During Force Thermo-OFF
• [COOL/DRY] operation is unavailable because the other
indoor unit operates with [HEAT] mode.
• [HEAT] operation is unavailable because COOL priority
(SW11-bit1 of the Outdoor I/F P. C. board is ON) is set and
the other indoor unit operates with [COOL/DRY] mode.
3) The above indoor units that cannot operate stay in
Thermo-OFF status.
4) The indoor fan stops because the system performs
[Recovery operation for heating refrigerant (Oil)].
<PRE-HEAT>
Displayed on the remote controller
The indoor fan stops in order to prevent discharge of cool air
when heating operation started or during heating operation.
(including the defrost operation during thermo-OFF)
1) Selection of the contents that can be operated by the remote controller at the
indoor unit side is possible according to setting at the central controller side.
2) Setting contents
• In case of TCC-LINK central control
Operation from
TCC-LINK
central control
Individual
[Central 1]
[Central 2]
[Central 3]
[Central 4]
Operation on RBC-AMT32E
ON/OFF
Operation
Timer
Temp.
Air speed
Air direction
setting
selection
setting
setting
setting
setting
¡
¡
¡
¡
¡
¡
×
¡
×
¡
¡
¡
×
×
×
×
¡
¡
¡
×
¡
×
¡
¡
¡
×
¡
¡
¡
¡
On
RBC-AMT32E
No display
[Central control
]
display
(
¡
: Operation possible
×
: Operation impossible)
• In case of wired remote controller type, [Central control
] display (Goes on) in the
central control mode
• Display flashes when an item of the operation prohibited was changed on the remote controller.
• In case of wireless remote controller type, the display lamp does not change but the
contents that can be operated are same in the central control mode.
(
∗
1) The operation from the wireless remote controller in the central control mode is
notified with the receiving sound, Pi, Pi, Pi, Pi, Pi (5 times).
(
∗
1)
If the operation select modes are different in the central 2 to 4 from those at the central
controller side, the operations Temp. Setting, air volume setting, and air direction setting are
inoperable.
Remarks
•
<
>
display
No display for wireless
remote controller
•
< >
display
38