Check method
On the remote controller (Wired remote controller, Central control remote controller) and the interface P.C. board of
the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.
board) to display the operation is provided. Therefore the operation status can be known. Using this self-diagnosis
function, a trouble or position with error of the air conditioner can be found as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See “Wired remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor 7-segment display” in the list.
• In case of check from indoor unit with wireless remote controller: See “Sensor block display of receiving unit” in the
list.
AI-NET: Artifi cial Intelligence.
IPDU: Intelligent Power Drive Unit
: Lighting,
: Flashing,
: Goes off
ALT.: Flashing is alternately when there are two fl ashing LED.
SIM: Simultaneous fl ashing when there are two fl ashing LED.
Check code
Wireless remote controller
Check code name
Judging
device
Wireless
remote
controller
display
Outdoor 7-segment display
Sensor block display of
receiving unit
Auxiliary code
OPERATION TIMER
PRE.DEF.
Flash
E01
—
—
Communication error between indoor
and remote controller (Detected at
remote controller side)
Remote
controller
E02
—
—
Remote controller transmission error
Remote
controller
E03
—
—
Communication error between indoor
and remote controller (Detected at
indoor side)
Indoor
E04
—
—
Communication circuit error between
indoor/outdoor (Detected at indoor side)
Indoor
E06
E06
No. of indoor units in which
sensor has been normally
received
Decrease of No. of indoor units
I/F
—
E07
—
Communication circuit error between
indoor/outdoor (Detected at outdoor
side)
I/F
E08
E08 Duplited indoor addresses
Duplicated indoor addresses
Indoor / I/F
E09
—
—
Duplicated main remote controllers
Remote
controller
E10
—
—
Communication error between indoor
MCU
Indoor
E12
E12
01: Indoor/Outdoor
communication
02: Communication between
outdoor
units
Automatic address start error
I/F
E15
E15
—
Indoor is nothing during automatic
addressing
I/F
E16
E16
00: Capacity over
01 ~:No. of connected units
Capacity over / No. of connected
indoor units
I/F
E18
—
—
Communication error between indoor
units
Indoor
E19
E19
00: Header is nothing
02: Two or more header units
Outdoor header units quantity error
I/F
E20
E20
01: Outdoor of other line
connected
02: Indoor of other line
connected
Other line connected during automatic
address
I/F
E22
E22
—
Reduction in number of heat storage
units
I/F
E23
E23
—
Sending error in communication
between outdoor units
I/F
E25
E25
—
Duplicated follower outdoor addresses
I/F
E26
E26
No. of outdoor units which
received signal normally
Decrease of No. of connected outdoor
units
I/F
E28
E28 Detected outdoor unit number
Follower outdoor unit error
I/F
E31
E31 Number of IPDU (*1)
IPDU communication error
I/F
F01
—
—
ALT
Indoor TCJ sensor error
Indoor
F02
—
—
ALT
Indoor TC2 sensor error
Indoor
F03
—
—
ALT
Indoor TC1 sensor error
Indoor
F04
F04
—
ALT
TD1 sensor error
I/F
F05
F05
—
ALT
TD2 sensor error
I/F
F06
F06
01: TE1 sensor
02: TE2 sensor
ALT
TE1 sensor error
TE2 sensor error
I/F
F07
F07
—
ALT
TL sensor error
I/F
F08
F08
—
ALT
TO sensor error
I/F
F10
—
—
ALT
Indoor TA sensor error
Indoor
F12
F12
—
ALT
TS1 sensor error
I/F
F13
F13
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT
TH sensor error
IPDU
F15
F15
—
ALT
Outdoor temp. sensor miscabling (TE,
TL)
I/F
F16
F16
—
ALT
Outdoor pressure sensor miscabling
(Pd, Ps)
I/F
F22
F22
—
ALT
TD3 sensor error
I/F
F23
F23
—
ALT
Ps sensor error
I/F
F24
F24
—
ALT
Pd sensor error
I/F
F29
—
—
SIM
Indoor other error
Indoor
F31
F31
—
SIM
Indoor EEPROM error
I/F
H01
H01
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
Compressor break down
IPDU
H02
H02
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
Magnet switch error
Overcurrent relay operation
Compressor trouble (lock)
MG-SW
Overcurrent
relay
IPDU
H03
H03
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
Current detect circuit system error
IPDU
H04
H04
—
Comp 1 case thermo operation
I/F
H06
H06
—
Low pressure protective operation
I/F
H07
H07
—
Oil level down detective protection
I/F
H08
H08
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
05: TK5 sensor error
Oil level detective temp sensor error
I/F
H14
H14
—
Comp 2 case thermo operation
I/F
H15
H15
—
TD2 sensor miswiring
I/F
H16
H16
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
05: TK5 oil circuit system error
Oil level detective circuit error
Magnet switch error
Overcurrent relay operation
I/F
MG-SW
Overcurrent
relay
H25
H25
—
TD3 sensor miswiring
I/F
108