(Repeats)
No.
16
17
Item
Louver control
Hi POWER
operation
(Wireless remote
controller specific
operations)
Outline of specifications
1) Louver position setup (Wired type)
• The louver position can be set up in the following operation range.
In cooling/dry operation
In heating/fan operation
• In group operation, the louver positions can be set up collectively
or individually.
2) Swing setup
• The following display is repeated.
In all operations
• In group operation, the louver positions can be set up collectively
or individually.
3) FIX setup (Wireless type)
Keep pushing or pushing briefly the FIX button to move the louver in
the desired direction.
Operating angle of louver will be different during cooling, dry and
heating operation.
4) When the unit stopped or the warning was output, the louver is
automatically set to full closed position.
5) When PRE-HEAT
is displayed (Heating operation started or
defrost operation is performed), heating thermo is off, the louver is
automatically set to
closed
.
When you push the Hi POWER button during cooling, heating or
A operation, the air conditioner will start the following operation.
• Cooling operation
Performs the cooling operation at 1°C lower than the setting
temperature.
Only when the fan speed before the Hi POWER operation is not
high, the fan speed will be increased.
Remarks
• [Hi POWER]
Display
39
When the Hi POWER is selected, running time for the damper control
is cleared once.
• Heating operation
Performs the heating operation at 2°C higher than the setting
temperature.
Only when the fan speed before the Hi POWER operation is not
high, the fan speed will be increased.
Содержание MML-AP0074NH-E
Страница 14: ...5 Hz Φ Φ Φ 2 SPECIFICATIONS 2 1 Indoor Unit 13 ...
Страница 15: ...6 Hz Φ Φ Φ 14 ...
Страница 132: ...TOSHIBA CARRIER THAILAND CO LTD ...