65
8-4.
Outdoor unit
control
5-2) Hot water supply and heating fan control
1) The TE sensor, TO sensor and operation frequency control the outdoor fan.
(The minimum W1 to the maximum are controlled according to the table below.)
2) For 3 minutes after the start, the maximum fan tap for each zone that is shown in the following table is fixed. After
that, the fan is controlled according to the TE sensor temperature.
3) If TE
≥
24 °C continues for 5 minutes, the operation stops. No error code is displayed for this; the status is the same as
the usual thermostat off. The operation restarts after 150 seconds. This intermittent running is not abnormal.
NOTE
If the heat-pump was thermo-off, the out-door fan motor (up/down) continue to run 10 min with W3 rotation.
When the water pump of hydro unit turns on, the fan motor will operate sensing value of outside air temperature (TO).
Item
Operation flow and applicable data, etc.
TE [°C]
24
21
18
15
-1 tap/20 secs (to W1)
-2 tap/20 secs (to W1)
-2 tap/20 secs (to W1)
Stop time count
Number of revolutions hold
+ 1 tap/20 secs
(Up to the maximum tap for each zone)
Temperature range
Less than 20 Hz
20 Hz or more to less
than 45 Hz
45 Hz or more
Maximum
Maximum
Maximum
30 °C
≤
TO
W4
W4
W6
25 °C
≤
TO < 30 °C
W5
W5
W7
20 °C
≤
TO < 25 °C
W6
W7
W8
10 °C
≤
TO < 20 °C
W7
W8
W9
5 °C
≤
TO < 10 °C
W9
WA
WA
-3 °C
≤
TO < 5 °C
WA
WA
WB
-10 °C
≤
TO < -3 °C
WB
WB
WB
TO < -10 °C
WD
WD
WD
TO abnormal
WD
WD
WD