93
[E04] Error
[F03] Error TC sensor failure
Outdoor unit operates
Yes
Check water heat exchanger
control board
If defective, replace it
Check outdoor control board
If defective, replace it
No
Yes
Hydro unit
Internal wiring and
connecting wire (1, 2, 3)
are correct
Correct wiring and
connecting wire
No
Yes
CN04 connector
and terminal block (1, 2, 3) wiring
are normal
Correct connector and
terminal block wiring
No
Yes
When power is
on again, D502 (Amber LED)
blinks
Check water heat
exchanger board
If defective, replace it
No
Yes
Correct TC sensor
connection
Replace TC sensor
No
No
TC sensor
connector (CN203) is
connected
Yes
TC sensor
resistance characteristic
is normal
Yes
Start
Replace water heat exchange control board