164
2. Outdoor Unit
HWS-P805HR-E, P1105HR-E
No.
Exchange parts
name
Work procedure
Remarks
1
Common procedure
NOTE
Wear gloves when performing the work.
Failure to do so may cause an injury when accidentally
contacting the parts.
1. How to remove
1) Stop the operation by remote controller and turn
off the breaker.
2) Remove the front panel.
(Hex Ø4 × 10, 2 screws)
• After unscrewing the screws, remove the front
panel while pulling it downward.
3) Disconnect the power source cable and
connecting cables between hydro and outdoor
from the cord clamp and terminals.
4) Remove the top board.
(Hex Ø4 × 10, 5 screws)
2. How to attach
1) Attach the top board.
(Hex Ø4 × 10, 5 screws)
2) Connect the power source cable and connecting
cables between hydro and outdoor to the terminal,
and fix them with the cord clamp.
NOTE
The power source cable and connecting cable between
hydro and outdoor units must be fixed along the
connecting piping by using a cable tie so that the
cables do not contact the compressor, gas side valve,
gas side piping and outlet pipe.
3) Attach the front panel.
(Hex Ø4 × 10, 2 screws)
Front panel
Top board