Auto-Curve temperature shift
• This function is available only for the header remote controller.
• The set temperature can be shifted in the range of ±5K of the current setting.
1
Press the [
] / [
] button to select “Auto mode” on the MENU
screen.
2
Press the [ ] button for 4 seconds or longer to enter the setting mode. The function code setting
screen appears.
FC No. 27: Shifted temperature (Range: -5 ~ +5, Default: 0)
3
Press the [
] button to select Data value, then press the [
] / [
] button to adjust the
temperature between -5K to +5 K.
4
Press the [
] button. The set temperature is registered.
Auto mode
MENU(1/2)
Schedule timer
Night setback
Silent mode
Hot water boost
SET
Auto mode
FC No.
Data
FIX