<How to set Frost protection operation end time>
• This function is available only for the header remote controller.
1
Press the [
] / [
] button to select “Frost protection” on the
MENU screen.
2
Press the [ ] button for 4 seconds or longer to enter the setting mode. The function code setting
screen appears.
FC No. 12: End days (Range: 0~20, Default: 0)
13: End times (Range: 0~23, Default: 0)
ex)
Code No. 12: 05
13: 13 = 5 days 13 hours
3
Press the [ ] / [ ] button to select FC number or Data, then press the [
] / [
] button
to set the value.
4
Press the [
] button. The set value is registered.
MENU(2/2)
Frost protection
Setting
Information
SET
Anti bacteria
Frost protection
FC No.
Data
FIX