49
8-3.
Hydro Unit Control
2) Control at the time of heating heater operation
• Controlled Object: Backup heater, Booster heater
The backup heater control starts when 13 minutes has passed after the heating heat pump operation started.
The backup heater control increases, decreases, or maintains the number of heaters every 10 minutes (FC)
depending on the difference between the heating set temperature (TSC_F) and the heater outlet temperature
(THO). Note that when the heating set temperature (TSC_F) is reached, the unit stops energizing the heater.
HWS-**M3-E model has the backup heater 1 of 3 kW only.
HWS-**T6-E model has the backup heater 2 of 3 kW. (Total 6 kW)
Booster heater operation come only output signal. (Booster heater activate under heater only mode)
Related FC
2-3) Heater control at the time of defrosting
• Object to be controlled: Backup heater
When a defrosting operation starts during the heating heat
pump operation, the unit energizes a backup heater (3 kW)
according to the heater outlet temperature sensor (THO) and
the set temperature (TSC_F) as shown in Figure.
1) When the heater outlet temperature sensor (THO) drops to
the temperature of 2 °C below the TSC_F-
β
, the backup
heater is energized.
β
can be changed for energy saving.
Defrosting ends according to the usual heater control.
Related FC
2-4) Forcible heater energization
To prevent freeze, the unit energizes or stops energizing a backup heater (3 kW) regardless of the unit status, not
operated or in operation.
• Object to be controlled: Backup heater
1) Energization start condition: TWO < 4 or TWI < 4 or THO < 4
2) Energization stop condition: TWO
≥
5 and TWI
≥
5 and THO
≥
5
Defrosting ends according to the usual heater control.
Item
Operation flow and applicable data, etc.
70
TSC_F-0
TSC_F-2
TSC_F+2
THO
E zone
D zone
C zone
B zone
A zone
Diff : 2K
Diff : 2K
Diff : 2K
Abnormality detection
Heater off
KEEP
Heater output down every
5, 10, 15, or 20 minutes
Heater output up every
10, 20, 30, or 40 minutes
Status
Heater ON/OFF
Heater 1
Backup heater 3 kW = ON
Heater 2
Backup heater 9 kW = ON
Heater 3
Heater 2 + Booster heater
FC No.
Setting item
Default
Setting available range
20
Hot water supply heat pump start temperature
38 °C
20-45 °C
21
Hot water supply heat pump stop temperature
45 °C
40-50 °C
33
Heater control of down time
1:10 min
0:5 min 2:15 min 3:20 min
34
Heater control of up time
0:10 min
1:20 min 2:30 min 3: 40 min
TSC_F - β
THO
Heater OFF
Heater ON
diff: 2K
Status
Heater ON/OFF
Heater 1
Backup heater 3 kW = ON
FC No.
Setting item
Default
Setting available range
B9
β
: 0 = 0K, ..., 4 = 40K
Recommendation :
β
= 2(20K)
0K
0K - 40K