[P15]
<Indication 1> <Indication 2>
[Gas leakage detection]
Check code
Outdoor LED
indication
Check and Action procedure
(No specific description indicates outdoor unit parts.)
Check outdoor control board
If defective, replace it
No gas leakage.
Appropriate refrigerant amount.
Correct defective portion
Re-charge refrigerant
No
Yes
Pulse motor valve is normal.
Correct defective portion
Replace defective parts
No
Yes
Service valve is fully opened.
Open fully service valve
No
Yes
Piping collapse
Repair or replace pipe
Yes
No
Temperature sensor check
Discharge sensor CN603
Suction sensor CN600
Correct connector
Replace sensor
NG
OK
PC board
P805HR-E, P1105HR-E (MCC-1571)