Installation example of water circuit
The water flowing for a system without buffer tank ((1), (2), (3), (5)) requires18 /min (P805XWH 13 /min) or more.
This water flowing requires 5 or more branches of Floor heating or Radiator etc.
Less than 5 branches may cause a flow deficiency. In this case, please provide a buffer tank and secondary pumps
as shown in (4).
Please check how to install the boiler (See page 40)
(1)
(2)
(3)
(4)
(5)
(6)