120
Function code table
FC
Item
Details
Factory default
01
Water heat exchanger capacity *1
0012: P805XWH**-E
0015: P1105XWH**-E
Depends on type
02
Cooling/Non-cooling switching
0000: Cooling
0001: Not cooling
0000: Cooling
08
Hot water boost operation time (operating time)
0003: 30 min
-
0018: 180 min
0006: 60 min
09
Hot water boost set temperature
0040: 40 °C
-
0080: 80 °C
0075: 75 °C
0A
Anti bacteria set temperature
0065: 65 °C
-
0080: 80 °C
0075: 75 °C
0B
Anti bacteria holding time
0000: 0 min
-
0060: 60 min
0030: 30 min
0C
Mixing valve drive time
0003: 30 sec
-
0024: 240 sec
0006: 60 sec
0F
Hot water HP allowance while c hot water
supply
0000: Not allow
-
0001: Allow
0000: Not allow
18
Upper limit of cooling set temperature
0018: 18 °C
-
0030: 30 °C
0025: 25 °C
19
Lower limit of cooling set temperature
0007: 7 °C
-
0018: 20 °C
0007: 7 °C
1A
Upper limit of heating (ZONE1) set temperature
0037: 37 °C
-
0060: 60 °C
0060: 60 °C
1B
Lower limit of heating (ZONE1) set temperature
0020: 20 °C
-
0037: 37 °C
0020: 20 °C
1C
Upper limit of heating (ZONE2) set temperature
0037: 37 °C
-
0060: 60 °C
0060: 60 °C
1D
Lower limit of heating (ZONE2) set temperature
0020: 20 °C
-
0037: 37 °C
0020: 20 °C
1E
Upper limit of hot water set temperature
0060: 60 °C
-
0080: 80 °C
0075: 75 °C
1F
Lower limit of hot water set temperature
0040: 40 °C
-
0060: 60 °C
0040: 40 °C
20
Hot water HP start temperature
0020: 20 °C
-
0045: 45 °C
0038: 38 °C
21
Hot water HP stop temperature
0040: 40 °C
-
0050: 50 °C
0045: 45 °C
22
Priority mode Hot water supply/Heating switching
temperature
-0020: -20 °C
-
0020: 20 °C
0000: 0 °C
23
Boiler output enable switching temperature
-0020: -20 °C
-
0020: 20 °C
-0010: -10 °C
24
Outside air temperature for hot water temperature
compensation start
-0020: -20 °C
-
0010: 10 °C
0000: 0 °C
25
Hot water temperature compensation value
0000: 0K
-
0015: 15K
0003: 3K
26
Night setback change temperature range
0003: 3K
-
0020: 20K
0005: 5K
27
Set temperature shift with heating Auto
-0005: -5K
-
0005: 5K
0000: 0K
29
Outside air temperature T1 temperature
-0015: -15 °C
-
0000: 0 °C
-0010: -10 °C
2B
Outside air temperature T3 temperature
0000: 0 °C
-
0015: 15 °C
0010: 10 °C
2C
Set temperature A with outside air temperature of T0
0020: 20 °C
-
0060: 60 °C
0040: 40 °C
2D
Set temperature B with outside air temperature of T1
0020: 20 °C
-
0060: 60 °C
0035: 35 °C
2E
Set temperature C with outside air temperature of 0 °C 0020: 20 °C
-
0060: 60 °C
0030: 30 °C
2F
Set temperature D with outside air temperature of T3
0020: 20 °C
-
0060: 60 °C
0025: 25 °C
30
Set temperature E with outside air temperature of 20 °C 0020: 20 °C
-
0060: 60 °C
0020: 20 °C
31
Zone2 ratio with Zone1 as Auto
0000: 0%
-
0100: 100%
0080: 80%
33
Hydro unit backup heater down time
0000: 5 min
0002: 15 min
0001: 10 min
0003: 20 min
0001: 10 min
34
Hydro unit backup heater up time
0000: 10 min
0002: 30 min
0001: 20 min
0003: 40 min
0000: 10 min
3A
Frost protection function Invalid/Valid
0000: Invalid
0001: Valid
0001: Valid
3B
Frost protection set temperature
0008: 8 °C
-
0020: 20 °C
0015: 15 °C
3C
2-way valve operation (logical reverse) control
0000: Energised during cooling
0001: Not energised during cooling
0000: Activate during
cooling
3E
Heating HP/Boiler priority switching when using boiler
0000: Priority on HP
0001: Priority on boiler
0000: Priority on HP
40
Activate/deactivate room temperature control
0000: Deactivate
0001: Activate
0000: Deactivate
*1 FC_01 is needed for PCB replacement or function code reset procedure has been completed.
*2 System restart with remote controller.
*3 Restart in the mode when stopping.
*4 In addition, it is enable only when switch 2-3 is set to “OFF” and FC61 is set to “3”.