4) Cooling operation
1. Purpose
Cooling
2. Details
This section performs
cooling operation
according to cooling
conditions specified for
the steps on the left.
3. Operations
1) By pressing the [
]
button on the remote
controller, the hydro
unit controller starts to
transmit a cooling
operation signal to the
outdoor unit.
2) The hydro unit
controller performs the
operation controls
shown on the left while
also controlling the
circulation pump, water
2-way valve, and water
3-way valve.
3) The outdoor unit
controls the
compressor, outdoor
fan motor, pulse motor
valve, and 4-way valve
based on the operation
signals transmitted by
the hydro unit.
Item
Operation flow and applicable data, etc.
Operation description
Hydro unit
control
Circulation pump "ON/OFF" control
Water 3-way valve control
Water 2-way valve control
Cooling temperature: 7 °C to 25 °C
Number of compressor revolutions control
Number of outdoor fan motor revolutions control
Pulse motor valve control
4-way valve control
Outdoor unit
control
Operation instruction
signal transmit
Cooling operation
start