48
8-3.
Hydro Unit Control
2) Heater control
2-1) Hot water supply operation
During a hot water heat pump operation, the unit energizes the hot water cylinder heater (2.7 kW) when all the
following conditions are met. Note that when the hot water supply set temperature (TSC_F) is reached, the unit stops
energizing the heater.
• When 30 minutes has passed after the hot water heat pump operation started.
• The water inlet temperature (TWI) reaches 50 °C.
• The hot water cylinder sensor reaches the HP_OFF temperature (45 °C-FC).
• The HP_ON temperature (38 °C-FC) is reached without the hot water HP status.
• Hot water boost operation is in progress.
2-2) Heating operation
1) Heater control at the time of heat pump operation
• Object to be controlled: Backup heater
The backup heater control starts when 13 minutes has passed after the heating heat pump operation started and
select the ZONE (A-D). The backup heater control increases, decreases, or maintains the number of heaters
every 10 minutes (FC) depending on the difference between the heating set temperature (TSC_F) and the heater
outlet temperature (THO). When the heating set temperature (TSC_F) is reached, the hydro stops energizing
the backup heater.
(1) HWS-**M3-E model has the backup heater 1 of 3 kW only.
(2) HWS-**T6-E model has the backup heater 2 of 3 kW. (Total 6 kW)
• Restriction of backup heater energization during heating mode (For energy saving)
When outdoor temperature is higher than the reference valve, the backup heater is forcibly off during heating mode.
Related FC
Item
Operation flow and applicable data, etc.
85
Heat pump_OFF(45)
TSC_H
TTW
Z zone
Diff : 2K
TSC_H-4
Hot water boost
Heater on only with
Hot water boost in operation
Abnormality detection (A03 displayed)
Heat pump_ON (38 °C)
(Hot water heat pump)
Y zone
Heater off
X zone
Heater on
(Heater on without
hot water heat
pump)
70
TSC_F-2
TSC_F-4
TSC_F-0
(+2)
*1
THO
E zone
D zone
C zone
B zone
A zone
Diff : 2K
Diff : 2K
Diff : 2K
Abnormality detection (A02 displayed)
Heater off
KEEP
Heater output down every
5, 10, 15, or 20 minutes
Heater output up every
10, 20, 30, or 40 minutes
*1 HWS-P805 only
Status
Heater ON/OFF
Heater 1
Backup-heater 3 kW = ON
Heater 2
Backup-heater 9 kW = ON
FC No.
Setting item
Default
Setting available range
B8
Forcibly heater off
at TO
≥
A °C
no restriction
-5 ~ 20 °C
Содержание HWS-P1105HR-E
Страница 177: ...176 E P Box Assembly Hydro Unit 220 221 223 222 224 225 226 227 228 229 230 231 232 233 239 240 235 234 235 224 ...
Страница 181: ...180 Inverter Assembly HWS P805HR E P1105HR E 711 709 710 705 706 707 704 703 701 708 702 TD TL TS TE TO TO TE ...
Страница 183: ...182 ...
Страница 184: ...Copyright 2017 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...