Procedure 3: Writing Setting Data in EEPROM
(The EEPROM of the service P.C. board has been set to the factory default values.)
1
Push the
+
+
buttons simultaneously and hold for at least 4 seconds.
1
(This number
corresponds to the same number shown on the Remote Controller Operation Diagram.)
(Under UNIT No., ALL is displayed.)
At the same time, the CODE No. (DN code) 10 is displayed, and the fan of the indoor unit comes on, with the
louver swinging, depending on the model.
2
The
button allows you to moved the CODE No. (DN code) up/down by one place.
3
3
First, set the type and capacity codes of the indoor unit.
(Changing the type and capacity codes in EEPROM overwrites the factory default settings.)
(1) Set the CODE No. (DN code) to 10 (no change)
(2) Use the
button to select the type.
4
(For example, 0001 is for the 4-way air discharge cassette type.) - Refer to the attached table 1.
(3) Push the
button. (The display should change from flashing to steady.)
5
(4) Use the
button to set the CODE No. (DN code) to 11.
(5) Use the
button to set the capacity code.
(For example, 0012 is for the 027 type.) - See the CODE No. list.
(6) Push the
button. (The display should change from flashing to steady.)
(7) Push
button
(The
setting
completes
if the setting data are displayed.)
(8) Push the
button to bring the system back to normal off state.
6
4
Next, write any setting changes made on-site after installation, such as address settings, in the
EEPROM. Perform the tasks specified in step 1 again.
5
Use the
button to set the CODE No. (DN code) to 01 (To set filter sign lighting time)
6
Check the value displayed with the value jotted down in Procedure 1 and information proved by
the customer.
(1) If there is a discrepancy, change the setting in accordance with the jotted-down value, and push the
button.
(The display should change from flashing to steady.)
(2) If there is no discrepancy, do nothing.
7
Use the
button to change the CODE No. (DN code).
Again, check the value, and change the setting if necessary.
8
Repeat steps 6 and 7 until all the settings are checked.
9
When finished, push the
button to bring the system back to normal off state.
6
In the case of group operation, turn the unit off, reconnect the indoor-indoor group control wiring and CN41
connectors, and turn on all the indoor units.
(It takes the system about 1 minute to become responsive to remote controller operation.)
* CODE No. (DN code) go from 01 to FF with a few gaps along the way.
If you realize you have wrongly corrected a certain setting after pushing the
button, you can recover the initial
value by pushing the
button, provided that the CODE No. (DN code) is yet to be changed.
Содержание Carrier MMC-AP0181H2UL
Страница 11: ...11 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Страница 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Страница 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Страница 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Страница 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Страница 153: ...153 11 EXPLODED VIEWS AND PARTS LIST 1 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Страница 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Страница 164: ...164 11 2 Compact 4 way Cassette Type MMU AP0071MH2UL AP0091MH2UL AP0121MH2UL AP0151MH2UL AP0181MH2UL ...
Страница 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Страница 174: ...174 MMK AP0153H AP0183H AP0243H ...