<Operation procedure>
5
4
6
7
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
Cancel of line selection
When you want to
complete the setting
8
Finish
How to change all indoor addresses from an arbitrary wired remote controller
(It is possible when setting has finished by automatic addresses.)
Contents:
The indoor unit addresses in each identical refrigerant piping line can be changed from an
arbitrary wired remote controller.
~
Enter in address check/change mode and then change the address.
<Procedure>
Carry out this procedure during stop of system.
1
Push the timer time button
+
TEST
simultaneously for 4 seconds or more.
First line 1 and CODE No.
AC
AC
AC
AC
AC
(Address Change) are displayed.
Ø
2
Select line address using
UNIT LOUVER
/
SWING/FIX
button.
Ø
3
Push the
SET
button.
• The address of the indoor unit connected to the
refrigerant piping of the selected outdoor unit is
displayed and the fan and the louver are on.
First the current indoor address is displayed.
(Line address is not displayed.)
Ø
4
TIME
button push up/down the indoor
address of the SET DATA.
The set data is changed to a new address.
Ø
5
Push
SET
button to determine the set data.
Ø
6
Every pushing
UNIT LOUVER
button, the indoor unit
No. in the identical piping is displayed one
after the other.
• Only fan and louver of the selected indoor unit
start operation.
Repeat the Procedures
4
to
6
to change all the
indoor addresses so that they are not duplicated.
Ø
7
Push
SET
button.
(All the indications of LCD go on.)
Ø
8
Push
TEST
button and then the procedure
finishes.
If the UNIT No. is not call up here, the outdoor unit
in that line does not exist.
Push
CL
button to select a line again in the
Procedure
2
.
Содержание Carrier MMC-AP0181H2UL
Страница 11: ...11 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Страница 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Страница 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Страница 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Страница 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Страница 153: ...153 11 EXPLODED VIEWS AND PARTS LIST 1 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Страница 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Страница 164: ...164 11 2 Compact 4 way Cassette Type MMU AP0071MH2UL AP0091MH2UL AP0121MH2UL AP0151MH2UL AP0181MH2UL ...
Страница 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Страница 174: ...174 MMK AP0153H AP0183H AP0243H ...