67
(Example of 2-lines cabling)
(Real line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by connecting singly the
wired remote controller without remote controller inter-unit cable.
Group address
Individual
: 0000
Header unit
: 0001
Follower unit : 0002
In case of group control
Outdoor
Outdoor
Indoor
Indoor
Indoor
Indoor
Indoor
Header unit
Follower
unit
Line address
→
1
Indoor unit address
→
1
Group address
→
1
1
2
2
1
3
2
2
1
2
2
2
2
Address setup (Manual setting from Wired remote controller)
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push
SET
+
CL
+
TEST
buttons simultaneously
for 4 seconds or more.
2
(Line address)
Using the temperature setup
/
buttons, set
12
12
12
12
12
to the CODE No.
3
Using timer time
/
buttons,
set the line address.
4
Push
SET
button. (OK when display goes on.)
5
(Indoor unit address)
Using the temperature setup
/
buttons, set
13
13
13
13
13
to the CODE No.
6
Using timer time
/
buttons,
set 1 to the line address.
7
Push
SET
button. (OK when display goes on.)
8
(Group address)
Using the temperature setup
/
buttons, set
14
14
14
14
14
to the CODE No.
9
Using timer time
/
buttons,
set
0000
0000
0000
0000
0000
to Individual,
0001
0001
0001
0001
0001
to
Header unit and
0002
0002
0002
0002
0002
to follower unit.
10
Push
SET
button.
(OK when display goes on.)
11
Push
TEST
button.
Setup completes.
(The status returns to the usual stop status.)
Note 1)
When setting the line address from the remote controller, do not use Address 29 and 30.
As they are addresses which cannot be set to the outdoor unit, if they are set, the check code [E04] (Indoor/Outdoor
communication circuit error) is issued.
Note 2)
When an address was manually set from the remote controller and the central control over the refrigerant lines is
carried out, perform the following setting for the Header unit of each line.
• Set the line address for every line using SW13 and 14 on the interface P.C. board of the Header unit in each line.
• Except the least line address No., turn off SW30-2 on the interface P.C. board of the Header units in the lines
connected to the identical central control.
(Draw the terminal resistances of indoor/outdoor and central control line wirings together.)
• For each refrigerant line, connect the relay connector between Header unit [U1U2] and [U3U4] terminals.
• After then set the central control address.
(For setting of the central control address, refer to the Installation manual for the central control equipment.)
<Operation procedure>
1 2 3 4 5 6
1
3, 6, 9
END
11
2, 5, 8
4, 7, 10
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
7 8 9 10 11
END
Содержание Carrier MMC-AP0181H2UL
Страница 11: ...11 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Страница 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Страница 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Страница 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Страница 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Страница 153: ...153 11 EXPLODED VIEWS AND PARTS LIST 1 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Страница 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Страница 164: ...164 11 2 Compact 4 way Cassette Type MMU AP0071MH2UL AP0091MH2UL AP0121MH2UL AP0151MH2UL AP0181MH2UL ...
Страница 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Страница 174: ...174 MMK AP0153H AP0183H AP0243H ...