40
No.
6
7
Item
Prevention of cold
air discharge
Freeze prevention
control
(Low temp. release)
Outline of specifications
1. In heating operation, the higher temperature of TC2
sensor and TCJ sensor is compared with temperature
of TC1 sensor and then the lower temperature is
used to set the upper limit of the fan tap.
• When B zone has continued for 6 minutes, the
operation shifts to C zone.
• In defrost time, the control point is set to
+10.8°F[6°C].
1. In all cooling operation, the air conditioner operates
as described below based upon temp. detected by
TC1, TC2 and TCJ sensors.
2. In all cooling operation, the air conditioner operates
as described below based upon temp. detected by
TC2 and TCJ sensors.
• When “M” zone is detected for 45 minutes, the
thermostat is forcedly off.
• In “N” zone, the timer count is interrupted and held.
• When shifting to “M” zone again, the timer count
restarts and continues.
• If “L” zone is detected, the timer is cleared and
the operation returns to normal operation.
Reset conditions
1) TC1 > 54°F [12°C] and TC2 > 54°F [12°C] and TCJ
> 54°F [12°C]
2) 20 minutes passed after stop.
Remarks
TCJ: Temperature of indoor
heat exchanger sensor
• In D and E zones, priority
is given to remote control-
ler air speed setup.
• In A zone “ ” is displayed.
TC1: Temperature of indoor
heat exchanger sensor
( ) value:
When the power supply is
turned on, the Forced
thermo becomes OFF if the
temperature is less than
this indicated temperature.
P2
Q2
TC2, TCJ
41°F [5°C]
28°F [–2°C]
P1
Q1
TC1
50°C [41°F]
10°C [5°C]
32.5°F
[0°C]
TC2, TCJ
14°F
[–10°C]
7°F
[–14°C]
• When “J” zone is detected for 5 minutes, the
thermostat is forcedly off.
• In “K” zone, the timer count is interrupted, and held.
• When “
I
” zone is detected, the timer is cleared
and the operation returns to the normal operation.
• If forced thermo OFF by continuation of “J” zone,
operation of the indoor fan in LOW mode contin-
ues until it reaches the “
I
” zone.
It is rest when the following conditions are
satisfied.
E
B
A
A zone: OFF
B zone:
Over 86˚F [30˚C], below 90˚F [32˚C], ULTRA LOW (LL)
C zone:
Over 90˚F [32˚C], below 93˚F [34˚C], LOW (L)
D zone:
Over 93˚F [34˚C], below 97˚F [36˚C], MED (H)
E zone: HIGH (HH)
D
C
˚F [˚C]
97 [36]
93 [34]
90 [32]
86 [30]
75 [24]
68 [20]
P1
Q1
˚F
[˚C]
a
K
J
I
P2
Q2
˚F
[˚C]
L
N
M
Reset conditions
1) TC1 > 54°F [12°C] and TC2 > 54°F [12°C] and TCJ
> 54°F [12°C]
2) 20 minutes passed after stop.
Содержание Carrier MMC-AP0181H2UL
Страница 11: ...11 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Страница 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Страница 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Страница 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Страница 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Страница 153: ...153 11 EXPLODED VIEWS AND PARTS LIST 1 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Страница 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Страница 164: ...164 11 2 Compact 4 way Cassette Type MMU AP0071MH2UL AP0091MH2UL AP0121MH2UL AP0151MH2UL AP0181MH2UL ...
Страница 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Страница 174: ...174 MMK AP0153H AP0183H AP0243H ...