95
Check code
Location
of
detection
Description
System
status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check code
Sub-code
H16
H16
01: TK1 oil
circuit error
02: TK2 oil
circuit error
03: TK3 oil
circuit error
04: TK4 oil
circuit error
05: TK5 oil
circuit error
I/F
Oil level
detection
circuit error
All stop
No temperature
change is detected
by TK1 despite
compressor 1 having
been started.
• Check for disconnection of TK1 sensor.
• Check resistance characteristics of
TK1 sensor.
• Check for connection error involving
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equali
z
ing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
change is detected
by TK2 despite
compressor 2 having
been started.
• Check for disconnection of TK2 sensor.
• Check resistance characteristics of
TK2 sensor.
• Check for connection error involving
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equali
z
ing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
change is detected
by TK3 despite
compressor 3 having
been started.
• Check for disconnection of TK3 sensor.
• Check resistance characteristics of
TK3 sensor.
• Check for connection error involving
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equali
z
ing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
change is detected
by TK4 despite
compressor having
been started.
• Check for disconnection of TK4 sensor.
• Check resistance characteristics of
TK4 sensor.
• Check for connection error involving
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equali
z
ing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
change is detected
by TK5 despite
compressor having
been started.
• Check for disconnection of TK5 sensor.
• Check resistance characteristics of
TK5 sensor.
• Check for connection error involving
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E
valve.
• Check for clogging in oil equali
z
ing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
H25
H25
–
I/F
TD3 sensor
miswiring
(incomplete
insertion)
All stop
Air discharge
temperature (TD3)
does not increase
despite compressor
3 being in operation.
• Check installation of TD3 sensor.
• Check connection of TD3 sensor
connector and wiring.
• Check resistance characteristics of
TD3 sensor.
• Check for defect in outdoor P.C. board
(I/F).
Содержание Carrier MMC-AP0181H2UL
Страница 11: ...11 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Страница 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Страница 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Страница 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Страница 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Страница 153: ...153 11 EXPLODED VIEWS AND PARTS LIST 1 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Страница 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Страница 164: ...164 11 2 Compact 4 way Cassette Type MMU AP0071MH2UL AP0091MH2UL AP0121MH2UL AP0151MH2UL AP0181MH2UL ...
Страница 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Страница 174: ...174 MMK AP0153H AP0183H AP0243H ...