WARNINGS ON REFRIGERANT LEAKAGE
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.
NOTE 2 :
The standards for minimum room volume are as follows.
1) No partition (shaded portion)
2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening
without a door, or an opening 0.15% or larger than the
respective floor spaces at the top or bottom of the door).
3) If an indoor unit is installed in each partitioned room
and the refrigerant piping is interconnected, the
smallest room of course becomes the object.
But when a mechanical ventilation is installed
interlocked with a gas leakage detector in the smallest
room where the density limit is exceeded, the volume
of the next smallest room becomes the object.
Check of Concentration Limit
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its concentration will not exceed a set
limit.
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it contains
more than air, it poses the risk of suffocation if its
concentration should rise excessively. Suffocation from
leakage of R410A is almost non-existent. With the recent
increase in the number of high concentration buildings,
however, the installation of multi air conditioner systems
is on the increase because of the need for effective use
of floor space, individual control, energy conservation by
curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of
the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure
so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event
of an emergency, measures can be made before injury
can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
≤
Concentration limit (kg/m³)
Concentration limit
Compliance to the local applicable regulations and
standards for the concentration limit is required.
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should be
as charged in each independent device.
Important
Outdoor unit
e.g.,
charged amount (15kg)
e.g., charged
amount (10kg)
Indoor unit
Room A Room B Room C Room D Room E Room F
Outdoor unit
Refrigerant piping
Indoor unit
Outdoor unit
Refrigerant piping
Indoor unit
Very
small
room
Small
room
Medium
room
Large room
Mechanical ventilation device - Gas leak detector
Содержание Carrier MMC-AP0181H2UL
Страница 11: ...11 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Страница 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Страница 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Страница 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Страница 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Страница 153: ...153 11 EXPLODED VIEWS AND PARTS LIST 1 1 4 Way Cassette Type MMU AP0072H2UL AP0092H2UL AP0122H2UL ...
Страница 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Страница 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Страница 164: ...164 11 2 Compact 4 way Cassette Type MMU AP0071MH2UL AP0091MH2UL AP0121MH2UL AP0151MH2UL AP0181MH2UL ...
Страница 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Страница 174: ...174 MMK AP0153H AP0183H AP0243H ...