Operating Instructions
72
MAGNUM Brief PTI Test
LCD Display*
Description
Possible
Alarms
Duration
(Time)
PTI START
Activated
0.1A 0.0A 0.1A
Event Log for PTI begins.
All alarms are turned off. Alarm list is cleared.
All relays are turned off and air vent are closed.
None
2 seconds
SENSOR TEST
Activated
0.1A 0.0A 0.1A
All sensors must have values within their measuring
range.
00, 01, 02,
03, 04, 05,
32, 33, 34,
35, 97, 98,
99
5 seconds
EVAP FAN LOW TEST
SUP RET EVA
5.1C 5.0C 5.1C
1.1A 1.0A 1.1A
Condenser fan and compressor are turned off. With
evaporator fan on low speed, amp draw is measured
and compared to voltage and frequency:
•
MAGNUM and MAGNUM SL:
1.0 Amps approx. at 50 Hz,
1.0 Amps approx. at 60 Hz
•
MAGNUM 20:
1.5 Amps approx. at 50 Hz,
1.5 Amps approx. at 60 Hz
Amperes are recorded in the PTI log.
14, 15
10 seconds
EVAP FAN HIGH TEST
SUP RET EVA
5.1C 5.0C 5.1C
2.4A 2.3A 2.4A
Condenser fan and compressor are turned off. With
evaporator fan on high speed, amp draw is measured
and compared to voltage and frequency:
•
MAGNUM:
2.1 Amps approx. at 50 Hz,
2.5 Amps approx. at 60 Hz
•
MAGNUM SL and MAGNUM 20:
2.7 Amps approx. at 50 Hz,
3.2 Amps approx. at 60 Hz
Amperes are recorded in PTI log.
12, 13
10 seconds
PROBE TEST
SUP RET EVA
5.1C 5.0C 5.1C
2.4A 2.3A 2.4A
Evaporator fans operate on high speed for maximum 3
minutes. Then probe test runs until temperature
difference between sensors stops increasing. Maximum
temperature difference allowed:
•
Return/Evaporator: 1.5C (34.7F); return air sensor
temperature must be 0.5C (32.9F) above evaporator sensor
temperature.
•
Return/Supply: 0.8C (33.0F); return air sensor temperature
must be 0.5C (32.9F) above supply air temperature.
•
LH Supply/RH Supply (if equipped): 0.5C (32.9F).
115, 116,
117
1 minute
minimum
to
13 minutes
maximum
AFAM+ TEST
SUP RET EVA
5.1C 5.0C 5.1C
2.4A 2.3A 2.4A
Air vent is opened and verified that the motor is
operating. Evaporator fan is started and operating until
CO2 value is below 0.5 percent or 20 minutes.
57, 68, 69
10 seconds
minimum
to
20 minutes
maximum
* Readings may vary depending on voltage and temperature
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...