Diagnosis: Troubleshooting, Status Messages, Alarm Codes
166
Alarm Codes, Descriptions and Corrective Actions
NOTE: Sensors used with the MP-3000a
controller do not require calibration. Check
sensor resistance with an ohmmeter.
•
Shutdown Alarm (Level 1 Alarm): Alarm
light on display flashes and unit stops. Correct
alarm condition and acknowledge alarm
before restarting.
•
Check Alarm (Level 2 Alarm): Alarm light on
display flashes until alarm is acknowledged.
Alarm Codes, Descriptions and Corrective Actions
Code
Description
Corrective Action
00
Supply Air Sensor Open Circuit
(Check Alarm)
• When the sensor circuit resistance is higher than
100,000 ohms.
• When the temperature is below -70 C (-94 F).
• Indicates:
• Open circuit to left or right hand sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1 or cable No. 3
• Defective controller
• Identify defective sensor (left hand or right
hand) by viewing Data menu.
• Check sensor resistance between pins 1 and
2 on plug J15 and between pins 7 and 8 on
plug J14. Resistance must be 2,000 ohms at
25 C (77 F).
• Check cable No. 1 and cable No. 3 between
the controller and relay board.
• Check evaporator airflow.
01
Supply Air Sensor Short Circuit
(Check Alarm)
• When the sensor circuit resistance is lower than
200 ohms.
• When the temperature is above 80 C (176 F).
• Indicates:
• Short circuit to left or right hand sensor Defective
or wrong sensor Defective relay board
• Defective cable No. 1 or cable No. 3
• Defective controller
• Identify defective sensor (left hand or right
hand) by viewing Data menu.
• Check sensor resistance between pins 1 and
2 on plug J15 and between pins 7 and 8 on
plug J14. Resistance must be 2,000 ohms at
25 C (77 F).
• Check cable No. 1 and cable No. 3 between
the controller and relay board.
02
Return Air Sensor Open Circuit
(Check Alarm)
• When the sensor circuit resistance is higher than
100,000 ohms.
• When the temperature is below -70 C (-94 F).
• Indicates:
• Open circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Check sensor resistance between pins 3 and
4 on plug J15. Resistance must be 2,000
ohms at 25 C (77 F).
• Check cable No. 1 between controller and
relay board.
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...