Operating Instructions
95
To select ‘Auto Config’ to ON:
1. Enter ‘Configuration’ menu.
2. Use F2 or F3 key to scroll to ‘Auto Config’
menu line.
3. Press F4. The password line appears.
4. Press the following keys in this order:
•
F2, then A, then F4, then EXIT
5. Use F2 or F3 key to scroll to ON.
6. Press and hold F4 key until entry is complete.
7. Press ESC key to begin the ‘Auto Config’
sequence.
Once the ‘Auto Config’ is complete, and the
AFAM+ system has been found and configured
into controller memory, enter the desired settings.
If the damper motor or the gas analyzer is not
found during the ‘Auto Config’, use the diagram
below to verify the connections, supply voltages
and communication wring to the two components.
Also verify that the 9-pin serial cable is connected
from the AFAM board to the controller.