Operating Instructions
93
9. Press and hold the F4 key until the cursor
stops flashing. The new rate is recorded in the
datalogger and appears on the LCD display.
NOTE: If O2 setting is applicable, use above
instructions to set O2 value.
10. If ‘AFAM DELAY’ is required.
11. Press F2 key to scroll to ‘AFAM DELAY’.
12. Press F4 key to enter setting mode.
13. Enter the delay time in hours supplied by the
shipper.
14. Press and hold F4 key until cursor stops
flashing.
15. ‘CUSTOM’ will be displayed with the user
entered settings.
Changing the AFAM Mode to
‘UNITS’
1. Press Setpoint key. The setpoint menu appears
with the cursor on the ‘OPTISET’ line.
2. Press F3 key and scroll to the ‘AFAM’ line.
3. Press F4 key. Cursor moves to the end of the
command line and flashes.
4. Press F2 key to toggle to ‘UNITS’.
5. With ‘UNITS’ in the menu line, press and
hold the F4 key until the cursor stops flashing.
6. If ‘AFAM DELAY’ is required.
NOTE: If delay is required, ‘AFAM DELAY’
must be set before ‘AFAM RATE’.
7. Press F2 key to scroll to ‘AFAM DELAY’.
8. Press F4 key to enter setting mode.
9. Enter the delay time in hours supplied by the
shipper.
10. Press and hold F4 key until cursor stops
flashing.
11. Press F3 key to scroll to ‘AFAM RATE’.
12. Press F4 key to enter the setting mode.
13. Enter fresh air exchange rate supplied by the
shipper.
14. Press and hold the F4 key until the cursor
stops flashing. Door will calibrate to open
position and the new rate is recorded in the
datalogger and appears on the LCD display.
Changing the AFAM Mode to
‘MANUAL’
1. Press Setpoint key. The setpoint menu appears
with the cursor on the ‘OPTISET’ line.
2. Press F3 key and scroll to the ‘AFAM’ line.
3. Press F4 key. Cursor moves to the end of the
command line and flashes.
4. Press F2 key to toggle to ‘MANUAL’.
5. With ‘MANUAL’ in the menu line, press and
hold the F4 key until the cursor stops flashing.
6. Press F3 key to scroll to ‘AFAM RATE’.
7. Press F4 key to enter the setting mode.
8. Enter fresh air exchange rate supplied by the
shipper.
9. Press and hold the F4 key until the cursor
stops flashing. The new rate will be recorded
in the datalogger. The following LCD screen
will appear:
10. Use F3 key to open the door or F2 key to
close the door, move FAE door opening to
required opening based on requirement from
shipper using the door position reference decal
located on the frame of the unit, next to the
FAE door.
11. Press F4 key to accept door position.
NOTE: Failure to press the F4 key within 30
seconds will result in the vent door
remaining Closed or at a previously set
opening.
NOTE: When using ‘MANUAL’ mode, once
the door position is entered, the door will
remain open until it is physically changed or
the unit power has been OFF for more than
120 hours.
MOVE DOOR TO DESIRED
POSITION USING F2 / F3
PRESS F4 TO ACCEPT
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...