Electrical Maintenance
119
High Pressure Cutout Manifold
1. Connect the manifold gauge to the compressor
discharge service valve with a heavy duty,
black jacketed thick wall #HCA 144 hose with
6024 kPa, 60.24 bar, 900 psig working
pressure rating.
2. Operate the unit in Cool by performing a
Capacity 100 percent test from the Manual
Function Test menu of the controller.
3. Raise the discharge pressure of the
compressor by blocking the condenser coil
airflow. Temporarily cover the compressor
compartment, control box and power cord
storage compartment with cardboard to reduce
condenser coil airflow. This should increase
the discharge pressure enough to cause the
switch to open. When the switch opens:
•
The compressor should stop immediately.
NOTE: The discharge pressure should never
be allowed to exceed 3,447 kPa, 34.4 bar, 500
psig.
4. Be sure to remove the cardboard installed in
step 3.
If the HPCO switch fails to stop compressor
operation, replace the switch and repeat steps 1
through 4.
1.
Relief Valve
2.
O-ring
3.
Adapter Tee (Weather Head)
Figure 65: High Pressure Cutout Manifold
AXA0174
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...