Operating Instructions
59
Datalogger Menu
The Datalogger menu contains a list of functions
that display unit operating information recorded in
the MP-3000a datalogger. The following
functions are available:
Inspect Temperature Log:
Displays temperature
logs by time and date for the Setpoint, Supply
(Controlling Temp), Return, USDA1, USDA2,
USDA3 and ambient sensors, humidity sensor,
and event flags.
PTI State:
Displays days since last PTI Test.
Inspect PTI Log:
Displays results of last PTI test
including component volt and amps data and
sensor temperatures. Test values are recorded at
the start and end of the Chilled and Frozen mode
test.
Calibrate USDA Probe (Optional):
Sets a
temperature offset in the controller memory to
calibrate each USDA sensor to the controller.
Activate Tripstart:
Sets the date and time of the
trip start.
Set Log Time:
Sets the data log interval (1 minute
or 1/2, 1, 2 or 4 hours).
Inspect Event Log:
Displays important event logs
by time and date for events such as unit alarms,
power On/Off, setpoint change, clock reset, trip
start, defrost, etc.
A complete listing of the controller operating
menu is located on an 11” x 17” fold out on the
last page of the book.
Viewing the Datalogger Menu
With the
U
NIT
O
N
/O
FF
switch
O
N
and the LCD
display showing the standard display (setpoint):
1. Press the
F2
or
F3
key to enter the Main
menu.
2. Press the
F2
or
F3
key to scroll through Main
menu until [DATALOGGER] appears in LCD
display.
3. Press the
F4
key to access the Datalogger
menu. The first function appears in the LCD
display: [INSPECT TEMP LOG].
Figure 34: Datalogger Menu
4. Press
F2
or
F3
key to scroll to the desired
function:
•
[INSPECT TEMP LOG]
•
[PTI STATE]
•
[INSPECT PTI LOG]
•
[CALIBRATE USDA PROBE] (Optional)
•
[ACTIVATE TRIPSTART]
•
[SET LOG TIME]
•
[INSPECT EVENT LOG]
5. Press
F4
key to access the function selected.
Inspect Temp Log
With the
U
NIT
O
N
/O
FF
switch
O
N
and the LCD
display showing the standard display (setpoint):
1. Press the
F2
or
F3
key to enter the menu list.
2. Press the
F2
or
F3
key to scroll through Main
menu until [DATALOGGER] appears in LCD
display.
ALARMS
DATA
RMM STATE
Datalogger
Menu
- Inspect Temp Log
- PTI State
- Inspect PTI Log
- Calibrate USDA Probe
- Activate Trip Start
- Set Log Time
- Inspect Event Log
MAIN MENU
DATALOGGER
CONFIGURATION
MISC. FUNCTIONS
COMMANDS
NOTE: All screens are NOT
present on all units. The
screens that display on the
controller are determined by
the Controller Software
settings and the options
installed on the unit.
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...