Operating Instructions
54
Alarms Menu
The Alarm List menu displays alarm codes.
Alarm codes are recorded in the controller
memory to simplify unit diagnosis procedures.
Some alarm codes are only recorded during a
pretrip (PTI) test or function test. Fault codes are
retained by the controller in a non-volatile
memory. If the Alarm LED is on or flashing on
and off, enter the alarm list to view the alarm.
A complete listing of the controller operating
menu is located on an 11” x 17” fold out on the
last page of this manual.
Alarm Types
There are two types of alarms:
Shutdown Alarm (Level 1):
Alarm LED flashes
and unit stops. Shutdown alarms indicate the unit
has been stopped to prevent damage to the unit or
cargo. The condition must be corrected before
restarting the unit. Alarm code 56 (compressor
temperature too high) is a shutdown alarm.
Check Alarm (Level 2):
Alarm LED flashes until
alarm is acknowledged. Check alarms indicate
corrective action should be taken before a
problem becomes severe.
Alarm Code States
There are three alarm code states for Shutdown
and Check alarms:
Not Active:
An alarm condition has occurred but
no longer exists in the unit. Not Active means the
condition was corrected and did not recur for 1
hour; or the Unit On/Off switch was turned Off
and then On.
When a Not Active alarm code is acknowledged
(
F4
key pressed while alarm code appears in LCD
display): The Alarm LED will turn off and the
alarm code disappears from the alarm list.
Active:
An alarm condition has occurred and
continues to exist in the unit; or the alarm
condition occurred within the past 1 hour but does
not currently exist in the unit.
If the alarm condition no longer exists in the unit
and the alarm code is acknowledged: The Alarm
LED will turn off and the alarm code disappears
from the alarm list.
Figure 31: Alarms Menu
Acknowledge:
An alarm code has been viewed
and acknowledged in the alarm list. The Alarm
LED remains on but does not flash.
If the alarm condition is corrected: The Alarm
LED will turn off and the alarm code disappears
from the alarm list.
View the Alarm List Menu
With the
U
NIT
O
N
/O
FF
switch
O
N
and the LCD
display showing the standard display (setpoint):
1. Press the
F2
key to directly enter Alarms
menu. The first alarm code number, alarm
state and alarm description appears in LCD
display.
NOTE: Alarm codes are displayed in
sequential order, not in order of occurrence.
2. Write down the first alarm code. Then press
the
F2
key to view next alarm code when
more than one alarm code has been recorded.
ALARMS
Alarms Menu
• View and write down
all alarm code.
• Press F2 key to view
the next alarm code
• Clear alarm code by
correcting problem and
acknowledging the
alarm.
• To acknowledge an
alarm, press F4 key with
alarm code in display.
MAIN MENU
DATA
RMM STATE
DATALOGGER
CONFIGURATION
MISC. FUNCTIONS
COMMANDS
NOTE: All screens are NOT
present on all units. The
screens that display on the
controller are determined by
the Controller Software
settings and the options
installed on the unit.
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...