Operating Theory
108
Continuous Temperature Control
Operation
Chill Loads (Controller Setpoint at -9.9 C
[14.1 F] and Above):
The controller regulates the compressor, Digital
Control valve and electric heaters based on a
Control Temperature Differential (see “General
Theory of Operation” in this chapter for more
detail). This means the unit operating mode can
not be predicted based only on the setpoint and
supply air temperature.
At setpoints of -9.9 C (14.1 F) and above, the
controller operates the unit on:
•
Cool mode with Modulation.
•
Controller energizes the vapor injection valve
continuously when the cool capacity is 100
percent.
•
Heat mode (electric heaters pulse on and off
on a 60 second duty cycle).
•
Defrost mode (electric heaters on, evaporator
fans off).
A.
Cool with Modulation (control temperature
differential is above setpoint)
B.
Heat (electric heaters pulse on and off on a 60
second duty cycle if the control temperature
differential is below setpoint.)
C.
In-range (based on supply air temperature)
1.
Decreasing Temperature
2.
Setpoint
3.
Increasing Temperature
Figure 57: Chill Load Control Sequence
(Setpoints at -9.9 C [14.1 F] and Above)
AXA0156
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...