8.5
Emergency Stop
The emergency stop time is used in combination with multi-function digital input function #14 (Emergency stop).
When emergency stop input is activated the inverter will decelerate to a stop using the Emergency stop time
(00-26) and display the [EM STOP] condition on the keypad.
Note:
To cancel the emergency stop condition the run command has to be removed and emergency stop input
deactivated.
Example: Emergency Stop Switch set for input terminal S5 (03-04 = 14).
Terminal representation for 230V: 1 ~ 2 HP, 460V: 1 ~ 3HP
E
DO2
24VG
S2
S4
S6
S8
24V
+10V
GND
AI1
AI2
DO1
DOG
S1
S3
S5
S7
F1
F2
PI
AO1
AO2
E
Emergency
Stop Switch
Connect shield
to control
ground terminal
Emergency Stop
Common
/24VG
Control Terminals /
User Terminals
Terminal representation for 230V: 3 ~ 150 HP, 460V: 5 ~ 425HP,
575V:1~10HP, 690V:15~270HP
Emergency
Stop
Switch
Connect shield
to control
ground terminal
Emergency Stop
Common/
24VG
Control Terminals /
User Terminals
S1
S3
S5
S7
24V
+10V
GND
-10V
GND
DO1
DOG
S2
S4
S6
S8
F1
F2
PO
PI
GND
AO1
AI1
AO2
AI2
E
S(+)
S(-)
24VG
00-26
Emergency stop time
Range
0.0~6000.0 Sec