4-93
00-32
Application Selection **
Range
0:
General
1:
Water supply pump
2:
Conveyor
3:
Exhaust fan
4:
HVAC
5:
Compressor
6:
Hoist
- * Consult TECO for the settings
7:
Crane
- * Consult TECO for the settings
Note:
Before to set up 00-32 Application, it should do initialized setting (parameter 13-08) first. When setting
00-32, the I/O port function changed automatically. To avoid accident, be sure to confirm the I/O port signal of
inverter and external terminal control.
00-32=1: Water supply pump
Parameter
Name
Value
00-00
Control mode selection
0: V/F
11-00
Direction lock selection
1: Forward direction only
01-00
V/F curve selection
6(60Hz)
4(50Hz)
07-00
Momentary stop and restart selection 1: Enable
08-00
Stall prevention function
xx0xb: Stall prevention during deceleration