4-162
04-External Analog Input / Output Parameter
04-00
AI input signal type
Range
0:
AI1: 0~10V AI2: 0~10V/ 0~20mA
1:
AI1: 0~10V AI2: 4~20mA/ 2~10V
2:
AI1: -10~10V AI2: 0~10V/ 0~20mA
3:
AI1: -10~10V AI2: 4~20mA/ 2~10V
04-01
AI1 signal scanning and filtering time
Range
0.00~2.00 Sec
04-02
AI1 gain
Range
0.0~1000.0
%
04-03
AI1 bias
Range
-100~100.0
%
04-05
AI2 function setting
Range
0:
Auxiliary frequency
1:
Frequency Reference Gain
2:
Frequency Reference bias
3:
Output Voltage Bias
4:
Coefficient of acceleration and deceleration reduction
5:
DC braking current
6:
Over-torque Detection Level
7:
Stall prevention Level During Running
8:
Frequency lower limit
9:
Jump frequency 4
10:
Added to AI1
11:
Positive torque limit
12:
Negative torque limit
13:
Regenerative Torque Limit
14:
Positive / negative torque limit
15:
Torque command/ Torque limit (in speed control)
16:
Torque command/ Torque compensation
17:
PTC Overheat Protection
04-06
AI2 signal scanning and filtering time
Range
0.00~2.00Sec
04-07
AI2 gain
Range
0.0~1000.0
%
04-08
AI2 bias
Range
-100.0~1000.0
%
Refer to the followings for 04-00 AI input signal type:
If AI1 is 0~10V, set parameter 04-00 to 0 or 1.
If AI1 is -10~10V, set parameter 04-00 to 2 or 3.