4-46
Group 11: Auxiliary Parameters
Code Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
11-30
Variable Carrier
Frequency Max.
Limit
2~16
-
KHz
O
O
X
X
X
X
O
11-31
Variable Carrier
Frequency Min.
Limit
1~16
-
KHz
O
O
X
X
X
X
O
11-32
Variable Carrier
Frequency
Proportional Gain
00~99
00
-
O
O
X
X
X
X
O
11-33
DC Voltage Filter
Rise Amount
0.1~10.0
0.1
Vdc
O
O
X
X
X
X
X
*1
11-34
DC Voltage Filter
Fall Amount
0.1~10.0
5.0
Vdc
O
O
X
X
X
X
X
*1
11-35
DC Voltage Filter
Dead band Level
0.0~99.0
10.0
Vdc
O
O
X
X
X
X
X
*1
11-36
Frequency Gain of
OV Prevention
0.000~1.000
0.050
-
O
O
X
X
X
X
X
*1
11-37
**Frequency Limit
of OV Prevention
0.00~599.00
5.00
Hz
O
O
X
X
X
X
X
11-38
Deceleration Start
Voltage of OV
Prevention
230V: 200~400V
300
V
O
O
X
X
X
X
X
460V: 400~800V
700
575V: 500~1000V
900
690V: 600~1200V
1080
11-39
Deceleration Stop
Voltage of OV
Prevention
230V: 200~400V
350
V
O
O
X
X
X
X
X
460V: 400~800V
750
575V: 500~1000V
950
690V: 600~1200V
1140
11-40
OV Prevention
Selection
0: Disable
0
-
O
O
X
X
X
X
X
1: OV Prevention Mode 1
2: OV Prevention Mode 2
3: OV Prevention Mode 3
11-41
Selection of
Reference
Frequency
Disappearance
Detection
0: Decelerate to Stop
when Reference
Frequency Disappears
0
-
O
O
O
O
O
O
O
1: Operation is set by
Parameter 11-42
when Reference
Frequency Disappears
11-42
Disappearance
Level of
Reference
Frequency
0.0~100.0
80.0
%
O
O
O
O
O
O
O
11-43
Hold Frequency at
Start
0.0~599.0
0.0
Hz
O
O
O
O
O
O
O
11-44
Frequency Hold
Time at Start
0.0~10.0
0.0
s
O
O
O
O
O
O
O
11-45
Hold Frequency at
Stop
0.0~599.0
0.0
Hz
O
O
O
O
O
O
O
Содержание A510
Страница 25: ...3 11 Step 3 Make wire connections and place cover back Step 4 Fasten screw ...
Страница 38: ...3 24 690V 100 150HP 460V 125HP Power supply 690V 100 150HP M10 Terminal screw size T M10 M10 ...
Страница 45: ...3 31 3 690V 175HP 270HP ...
Страница 160: ...4 85 Frequency Reference Output Frequency 100 00 12 00 13 100 Figure 4 4 6 Frequency reference upper and lower limits ...