4-156
0%
100%
03-36
(Hz)
Pulse
output
Pulse output
items
Figure 4.4.29 Pulse output proportion
When setting 03-35 to 2 (output frequency) and setting 03-36 to 1 (0 Hz), PO's pulse output and the inverter
output frequency are sync.
For the pulse output signal level, please refer to figure 4.4.30.
+5V
PO
5V
0V
T1
T2
Pulse duty : T1= T2
Pulse train output : 0 to 32KHz , 2.2K
Ω
GND
0V
2.2K
Ω
Figure 4.4.30 Pulse output signal level
When 03-35 = 7 (PG pulse monitoring output), PG pulse output scaling is internally set 1:1, independent of the
scaling set in parameter 03-36.
Note:
When pulse output function is active, it is required to use the external pull-up resistor at the terminal of PO
(the upper limit current of PO is 50mA)
Application examples
Example A
: Speed follower from external PG
Use the pulse input signal as frequency reference or synchronization operation. Refer to Fig. 4.4.31.