4-275
20-15
ASR gain change frequency 1
Range
0.0~599.0 Hz
20-16
ASR gain change frequency 2
Range
0.0~599.0 Hz
20-17
Torque compensation gain at low speed
Range
0.00~2.50
20-18
Torque compensation gain at high speed
Range
-10~10
%
20-33
Detection Level at Constant Speed
Range
0.1~5.0 %
Parameter 20-33 is used when 20-07 is set to 0 and frequency command source is set to analog input mode.
Analog input signal, owing to the noise, will cause the system to determine the operation does not reach the
constant speed so the problem may occur. Thus, adjust parameter 20-33 to avoid this situation occurring..
The following figure an overview of the automatic speed regulator (ASR) block.
V/F + PG control mode:
The ASR function adjusts the output frequency to control the motor speed to minimize the difference between the
frequency reference and actual motor speed.
Frequency
Reference
Speed
Feedback
SFS
Fref
20-00
20-02
+
-
+
20-05
20-06
ASR Limit
20-07=1(during accel / decel)
. 20-07= 0 , or
. Speed control integral reset
(03-00 to 03-07= 43)
PG valid
PG invalid
(03-00 to 03-07= 42)
f
+
+
Fout
Output
Frequency
I
+
20-01
20-03
P
Figure 4.4.107 ASR block diagram (V/F + PG)
If one of the multi-function input (03-00 to 03-07) is set to 42 (PG is disabled), the input can be used to enable or
disable the speed control loop system (ASR).
Содержание A510
Страница 25: ...3 11 Step 3 Make wire connections and place cover back Step 4 Fasten screw ...
Страница 38: ...3 24 690V 100 150HP 460V 125HP Power supply 690V 100 150HP M10 Terminal screw size T M10 M10 ...
Страница 45: ...3 31 3 690V 175HP 270HP ...
Страница 160: ...4 85 Frequency Reference Output Frequency 100 00 12 00 13 100 Figure 4 4 6 Frequency reference upper and lower limits ...