4-187
07- 04
Direct Start at Power on
Range
0:
When the external run command is enabled, direct start at power up
1:
When the external run command is enabled, unable to direct start at power-up.
07-04=0:
The inverter will automatically start if the run command is active at power up.
07-04=1:
The inverter will not start if the run command is active at power up, warning STP1 will flash on the
keypad. In order to start the run command has to be cycled.
07- 05
Delay of Direct Start at Power on
Range
1.0~300.0 Sec
If 07-04=0, inverter will automatically start if the run command is active at power up after delay of Direct Start
timer has expired.
DANGER
:
When 07- 04= 0 and the external run is set (00-02/ 00-03=1),
When direct run on power up is enabled (07-04=0) and the inverter is set to accept an external run command
(00-02/00-03=1), the inverter will automatically start when power is applied and the run switch is ON.
It is recommend turning off the run switch when power to the inverter is turned off to avoid possibility of injury to
operators and damage to machines when power is applied to the inverter.
Note: If this mode is required for the application all safety measures must be taken to ensure safe
operation, including warning labels
.
Wen 07- 04= 1 and the external run is set (00-02/ 00-03=1),
When direct run is disabled (07-04 =1) and the inverter is set to accept an external run command (00-02/00-03=1),
the inverter will not start when power is applied, warning STP1 will flash on the keypad. To start the inverter turn
the run switch to OFF and back ON again.
07-06
DC injection braking starting frequency
Range
0.0~10.0 Hz
DC injection braking start frequency is the level the output frequency has to reach before DC braking injection
function is activated.
07-07
DC injection braking current
Range
0~100
%
DC Injection braking current as percentage of the inverter rated current. Increasing this level will increase the
amount of heat generated by the motor windings. Do not set this parameter higher than the level necessary to
hold the motor shaft.
07-08
DC injection braking time at stop
Range
0.00~10.00 Sec
Duration of DC injection braking during a stop operation. DC injection braking at stop is disabled when parameter
07-08 is set to 0 sec.
07-16
DC injection braking time at start