![TECO-Westinghouse A510 Скачать руководство пользователя страница 111](http://html.mh-extra.com/html/teco-westinghouse/a510/a510_instruction-manual_1072531111.webp)
4-36
Group 07: Start /Stop Parameters
Code Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
07-19
Direction-Detection
Speed Search
Operating Current
0~100
50
%
O
X
O
X
X
X
O
07-20
Speed Search
Operating Current
0~100
20
%
O
X
O
X
X
X
O
07-21
Integral Time of
Speed Searching
0.1~10.0
2.0
Sec
O
X
O
X
X
X
O
07-22
Delay Time of
Speed Searching
0.0~20.0
0.2
Sec
O
O
O
O
O
X
O
07-23
Voltage Recovery
Time
0.1~5.0
2.0
Sec
O
O
O
X
X
X
O
07-24
Direction-Detection
Speed Search
Selection
0: Disable
0
-
O
O
O
X
X
X
O
1: Enable
07-25
Low Voltage
Detection Time
0.00~1.00
0.02
Sec
O
O
O
O
O
O
O
07-26
Start-up Mode
Selection of SLV
Coast to Stop
0: Start with speed
search
0
-
X
X
O
X
X
X
X
1: Normal start
07-27
Start Selection
after Fault during
SLV Mode
0: Start with speed
search
0
-
X
X
O
X
X
X
X
1: Normal start
07-28
Start after External
Base Block
0: Start with speed
search
0
-
O
X
O
X
X
X
O
1: Normal start
07-29
Run Command
Selection at the
Action of DC
Braking
0: Not Allowable to Run
0
-
O
O
X
X
X
X
X
1: Allowable to Run
07-30
Low Voltage Level
Selection
0: Disable
0
-
X
X
X
O
O
X
X
1: Enable
07-31
**Low Voltage Run
Frequency
0.00~599.00
10.00
Hz
X
X
X
O
O
X
X
07-32
Speed Search
Mode Selection
0: Disable
0
-
O
O
O
O
X
X
X
1: Execute a Speed
Search at Power On
07-33
Start Frequency of
Speed Search
Selection
0: Maximum Output
Frequency of Motor
0
-
O
O
O
O
X
X
X
1: Frequency Command
*07-13 Low Voltage Detection Level, it is enable when 07-30 Low Voltage Level Selection set 0 (Enable)
and lower frequency limit set to 250V.This application is for
Emergency power supply (EPS)
* *If the maximum output frequency of motor is over 300Hz, the frequency resolution is changed to 0.1Hz
Содержание A510
Страница 25: ...3 11 Step 3 Make wire connections and place cover back Step 4 Fasten screw ...
Страница 38: ...3 24 690V 100 150HP 460V 125HP Power supply 690V 100 150HP M10 Terminal screw size T M10 M10 ...
Страница 45: ...3 31 3 690V 175HP 270HP ...
Страница 160: ...4 85 Frequency Reference Output Frequency 100 00 12 00 13 100 Figure 4 4 6 Frequency reference upper and lower limits ...