Note:
Terminal S1 must be closed for a minimum of 50ms to activate operation.
S1
S2
S7 Forward/Reverse
selection
24VG
Operation
(normally open
Momentary switch)
Stop
(Normally closed
Momentary
switch)
Stop Command
(Off: Stop)
Run Command
(On:Run)
Figure 4.4.2 wiring example of 3-wire
.
Time
Time
Time
Time
Run Command
Stop Command
Forward/Reverse
Command
Motor Speed
Off
Off
(Stop)
Off
(forward)
On (Reversal)
Stop
Forward
Reverse
Stop
Forward
On
>= 50ms
Figure 4.4.3 3-wire operation
■ 2-wire operation with hold function
To enable 2-wire operation with hold function set any of parameters 03-02 to 03-07 (terminal S3 ~ S8) to 53.
When this mode is enabled set terminal S1 (03-00=0) to forward and S2 (03-01=1) to reverse run command.