4-182
Example 3:
Automatic operation mode
– Single cycle and continue running at last speed of the cycle
In this example the inverter executes a single cycle and continue running at last speed of the cycle.
Parameter Settings:
06-00=
3 or 6 (Single cycle operation)
06-32~06-35=
1 (Forward)
06-36~06-47=
0
Other parameter =
Enter same setting as that of Example 1.
Freq.
50 Hz
30 Hz
15 Hz
20 Hz
20s
25s
30s
40s
05-01
06-01
06-02
06-15
06-16
06-17
06-18
06-31
Figure 4.4.54 Single cycle automatic operation (continuous)
06-00= 1 to 3:
After a stop the inverter will restart with the incomplete step when the run command is re-applied.
06-00= 4 to 6:
After a stop the inverter will restart with the first step of the cycle when the run command is re-applied.
1 to 3
RUN
STOP
RUN
Operation
Command
RUN
STOP
RUN
t
t
Output
Frequency
Operation
Command
Output
Frequency
Start new cycle
Continue with
incompleted step cycle
Output Frequen
cy
06-00
4 to 6
06-00
Notes:
- Acceleration/ deceleration time is set with the setting of 00-14 and 00-15 in the automatic operation mode.
- If the setting value of parameters 06-16~06-31 is 0, automatic operation mode is not active.