4-86
00-14
Acceleration time 1
Range
0.1~6000.0 Sec
00-15
Deceleration time 1
Range
0.1~6000.0 Sec
00-16
Acceleration time 2
Range
0.1~6000.0 Sec
00-17
Deceleration time 2
Range
0.1~6000.0 Sec
00-21
Acceleration time 3
Range
0.1~6000.0 Sec
00-22
Deceleration time 3
Range
0.1~6000.0 Sec
00-23
Acceleration time 4
Range
0.1~6000.0 Sec
00-24
Deceleration time 4
Range
0.1~6000.0 Sec
00-25
Switch-Over Frequency of Acceleration and Deceleration Time 1 and Time 4
Range
0.00~599.00 Hz
Acceleration time is the time required to accelerate from 0 to 100% of maximum output frequency.
Deceleration time is the time required to decelerate from 100 to 0% of maximum output frequency.
Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 Maximum frequency is set by parameter
01-16.
Note:
Actual acceleration and deceleration times can be affected by the inverter driven load.
The default values for the acceleration, deceleration times are dependent on the inverter size.
Size
Acceleration / Deceleration
Default Value
200V series
400V series
1~10HP
1~15HP
10s
15~20HP
20~30HP
15s
30~150HP
40~425HP
20s
Содержание A510
Страница 25: ...3 11 Step 3 Make wire connections and place cover back Step 4 Fasten screw ...
Страница 38: ...3 24 690V 100 150HP 460V 125HP Power supply 690V 100 150HP M10 Terminal screw size T M10 M10 ...
Страница 45: ...3 31 3 690V 175HP 270HP ...
Страница 160: ...4 85 Frequency Reference Output Frequency 100 00 12 00 13 100 Figure 4 4 6 Frequency reference upper and lower limits ...