4-257
16-03
Set / displayed contents
0
0.01 Hz
1
0.01 % (maximum output frequency 01-02=100%)
2
Frequency display unit is rpm
3 - 39
Reserved
00040 - 39999
Set the decimal point by using the fifth place.
i.e. □ □□□□
Sets full display scaling excluding decimals
Set the number of decimal places
00040 - 09999:
□□□□
(Integer only e.g. 1000 )
10001 - 19999:
□□□. □ (1 decimal place e.g. 10.0)
20001 - 29999:
□□. □□ (2 decimal places, e.g. 10.00)
30001 - 39999:
□. □□□ (3 decimal places, e.g. 10.000)
<example>
16-03
Display
Display unit
Display example
00040
–
09999
□□□□
use
16-04 setting
Example:
100 % speed is 0200
> set 16-03=00200 (from 05-01, 06-01 to 06-15,
set range from 0040 to 9999).
> set 16-04=0 (no unit)
10001
–
19999
□□□. □
Example:
100 % speed is 200.0 CFM
> set 16-03=12000 (05-01, 06-01 to 06-15, set
range from 0000 to 9999).
> set 16-04=2 (CFM)
> 60% speed will be displayed as 120.0 CFM
20001
–
29999
□□. □□
Example:
100 % speed is 65.00ºC
> set 16-03=26500 (05-01, 06-01 to 06-15, set
range from 0000 to 9999)
> set 16-04=20 (ºC)
> 60% of speed is displayed as 39.00 ºC
30001
–
39999
□. □□□
Example:
100 % speed is 2.555 m/s
> set 16-03=32555
> set 16-04=14 (m/s)
> 60% speed is displayed as 1.533 m/s