The minimum distance from flammable materials must be 200 mm. In case the floor
is made of flammable material (wood / parquet floor) it must be insulated with non-
flammable one.
The steel pipes for exhaust gases must be mounted at distance minimum 1.5 m. from
any flammable materials. We recommend the pellet stove to be installed as closer as
possible to the exhaust system (chimney). The pipe system for the exhaust gases
must be with maximum 3+1 T knees and maximum 3 m. from the horizontal flow
with minimum deviation 3-5%. After the place for installation is defined unpack the
unit and check the closing of the front door.
3.2. Connecting of outer tube for fresh air flow
For proper functioning and distribution of the temperature the pellet stove must
receive enough fresh air flow and to be well positioned (a special opening for fresh
air could be done for example). The opening for the fresh air must be minimum 100
cm2 and there should not be any obstacles on its way. Fresh air could be taken also
from other room which has its own constant ventilation and no other pellet stove or
similar heating system, which needs also fresh air flow. This room cannot be
bedroom, bathroom or any other room that are fire hazard for instance garages,
basements, stores etc. If the pellet stove in the room uses gas from an open system
or another source of harmful gases the air flow must come directly outside the room
from the environment.
Example: Connection of tube for fresh air flow directly from the outside
For proper functioning of the pellet stove it is recommended to make a direct
connection from outside the room with steel pipe 80 мм. with silicon gasket. The
part of the tube that goes outside the room must be situated downwards 90° - in this
way a protection against wind, water, etc. is achieved.
Keep the following distances:
1,5 m floor,
1,5 m horizontal,
0,3 m from doors, windows
2,0 m exhaust gases system.
The manufacturer bares no responsibility for damages caused by not keeping the
instructions.